Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Safety information
TheMCS – MULTI CONNECTION SYSTEMincludes connectors without breaking capacity in accordance with DIN EN 61984. When used as intended, these connectors must not be connected/disconnected when live or under load.When used as intended, these connectors must not be connected/disconnected when live or under load. The circuit design should ensure header pins, which can be touched, are not live when unmated.
Variants:
Other pole numbers
Clamping units
3
Total number of potentials
3
Number of connection types
1
Number of levels
1
Pin spacing
10.16?mm?/ 0.4?inches
Width
31.78?mm?/ 1.251?inches
Height
29.1?mm?/ 1.146?inches
Depth
95.6?mm?/ 3.764?inches
Variable coding
Yes
Anti-rotation protection
Yes
Contact type (pluggable connector)
Male connector/plug
Connector (connection type)
for conductor
Mismating protection
Yes
Plugging without loss of pin spacing
No
Locking of plug-in connection
none
Strain relief
Strain relief plate
Note (material data)
Information on material specifications can be found here
Color
light gray
Material group
I
Insulation material (main housing)
Polybutylene terephthalate (PBT)
Flammability class per UL94
V0
Clamping spring material
Chrome-nickel spring steel (CrNi)
Contact material
Electrolytic copper (ECu)
Contact plating
Silver
Fire load
0.868MJ
Actuator color
orange
Weight of insulation material
16.41g
Weight
41.5g
Limit temperature range
-60 … +120?°C
Processing temperature
-35 … +60?°C
ETIM 9.0
EC001284
ETIM 8.0
EC001284
ECCN
NO US CLASSIFICATION
PU (SPU)
15?pcs
Packaging type
box
Country of origin
DE
GTIN
4055143938174
Customs tariff number
8536694040
RoHS Compliance Status
Compliant,No Exemption
Ratings per
IEC/EN 60664-1
Rated voltage (III / 3)
1000V
Rated impulse voltage (III / 3)
8kV
Rated voltage (III/2)
1000V
Rated surge voltage (III/2)
8kV
Nominal voltage (II/2)
1000V
Rated surge voltage (II/2)
8kV
Rated current
76A
Legend (ratings)
(III / 2) ? Overvoltage category III / Pollution degree 2
Approvals per
CSA
Rated voltage UL (Use Group B)
600V
Rated current UL (Use Group B)
66A
Rated voltage UL (Use Group C)
600V
Rated current UL (Use Group C)
66A
Rated voltage (UL 1977)
600V
Rated current UL 1977
85A
Rated voltage CSA (Use Group B)
600V
Rated current CSA (Use Group B)
66A
Rated voltage CSA (Use Group C)
600V
Rated current CSA (Use Group C)
66A
Connection technology
Push-in CAGE CLAMP?
Actuation type
Lever
Solid conductor
0.75 … 16?mm2?/ 18 … 4?AWG
Fine-stranded conductor
0.75 … 25?mm2?/ 18 … 4?AWG
Fine-stranded conductor; with insulated ferrule
0.75 … 16?mm2
Fine-stranded conductor; with uninsulated ferrule
0.75 … 16?mm2
Strip length
18 … 20?mm?/ 0.71 … 0.79?inches
Number of poles
3
Conductor entry direction to mating direction
Test specification <br/>Railway applications – <br/>Rolling stock – <br/>Electronic equipment
DIN EN 50155 (VDE 0115-200):2022-06
Test procedure <br/>Railway applications – <br/>Rolling stock equipment – <br/>Shock and vibration tests
DIN EN 61373 (VDE 0115-0106):2011-04
Spectrum/Installation location
Service life test, Category?1, Class?A/B
Function test with noise-like vibration
Test passed according to Section 8 of the standard
Frequency
f1= 5 Hz to f2= 150 Hz
Acceleration
5g (highest test level used for all axes)
Test duration per axis
5 h
Test directions
X, Y and Z axes
Monitoring for contact faults/interruptions
Passed
Voltage drop measurement before and after each axis
Passed
Simulated service life test through increased levels of noise-like vibration
Test passed according to Section 9 of the standard
Extended test scope: Monitoring for contact faults/interruptions
Passed
Extended test scope: Voltage drop measurement before and after each axis
Passed
Shock test
Test passed according to Section 10 of the standard
Shock form
Half sine
Shock duration
30 ms
Number of shocks per axis
3 pos. und 3 neg.
Vibration and shock stress for rolling stock equipment
Passed

Specifications may be subject to change without notice