Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Protection type | IP20 | Test voltage | AC 3?kV;?50?Hz;?1?min |
Highest voltage for equipment U<sub>m</sub> | AC 720?Vrms | Feedthrough for measurement conductor | ? 28 mm |
Cable type | 2 x 0.5 mm2; fine-stranded | Color code | brown = S1; blue = S2 |
Cable length | 3m | Width | 57.2 mm / 2.25 inches |
Height | 67 mm / 2.64 inches | Depth | 49 mm / 1.93 inches |
Mounting type | Split-core current transformer (suspended) | Weight | 10g |
Ambient temperature (operation) | -10 … +55 °C | Ambient temperature (storage) | -20 … +70 °C |
Relative humidity | 5 … 85?% (without condensation) | Operating altitude (max.) | 2000m |
Conformity marking | CE | Standards/specifications | EN 61869-1 |
eCl@ss 10.0 | 27-21-09-02 | eCl@ss 9.0 | 27-21-09-02 |
ETIM 9.0 | EC002048 | ETIM 8.0 | EC002048 |
ECCN | NO US CLASSIFICATION | PU (SPU) | 1?pcs |
Packaging type | Box | Country of origin | NL |
Customs tariff number | 85043180888 | RoHS Compliance Status | Compliant,No Exemption |
Measured variable | Current | Rated continuous thermal current I<sub>cth</sub> | 100 % |
Rated short-time thermal current I<sub>th</sub> | 60 x IN/ 1 s | Rated surge current I<sub>dyn</sub> | 2.5 x Ith |
Rated frequency | 50 … 60?Hz | Primary rated current | 400?A |
Secondary rated current | 1A | Rated power S<sub>r</sub> | 0.2VA |
Accuracy class | 1 |