Product Model

857-369

In Stock
Last updated: 2025/4/18
wago 857-369

Selling Points

  • 1Wide Input Voltage Range: 24-230V AC/DC for versatile applications.
  • 2High Reliability: 5 x 10^6 switching operations ensure long-lasting performance.
  • 3Gold Contacts: Durable and reliable connections for consistent operation.
  • 4Shock- and Vibration-Resistant: Designed for use in railway operations and harsh environments.
  • 5Compact Design: 6 mm wide, easy to integrate into DIN-35 rail systems.
Product Details
857-369
wago

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Safety information
Adjacent devices of the same type are devices of the same design (series) that are arranged next to one another on the DIN-rail with the same orientation. An end stop (249-116) must be fitted to devices of other types for compliance with the reinforced insulation requirements.
Note
To prevent damaging the gold layer, 30 V switching voltages and 50 mA currents must not be exceeded. Higher switching power eventually evaporates the gold layer. The resulting deposits in the housing may reduce service life.
Rated voltage
300V
Rated surge voltage
4kV
Type of circuits
Mains circuits
Overvoltage category
III
Pollution degree
2
Dielectric strength (control/load circuit) (AC, 1?min)
3.51?kVrms
Dielectric strength (open contact) (AC, 1?min)
1?kVrms
Insulation type (control/load circuit)
Reinforced insulation (safe isolation)
Insulation type (between adjacent devices of the same type)
Double insulation (safe isolation)
Insulation type (to adjacent devices of different types)
Basic insulation
Protection type
IP20
Connection technology
Push-in CAGE CLAMP?
Solid conductor
0.34 … 2.5?mm2?/ 22 … 14?AWG
Fine-stranded conductor
0.34 … 2.5?mm2?/ 22 … 14?AWG
Fine-stranded conductor; with insulated ferrule
0.34 … 1.5?mm2?/ 22 … 16?AWG
Strip length
9 … 10?mm?/ 0.35 … 0.39?inches
Width
6?mm?/ 0.236?inches
Height
94?mm?/ 3.701?inches
Depth from upper-edge of DIN-rail
81?mm?/ 3.189?inches
Mounting type
DIN-35 rail
Mounting position
Horizontal (standing/lying); vertical
Note (material data)
Information on material specifications can be found here
Insulation material (main housing)
Polyamide (PA66)
Material group
I
Flammability class per UL94
V0
Fire load
0.544MJ
Weight
31.9g
Ambient temperature (operation at U<sub>N</sub>)
-25 … +70 °C
Ambient temperature (storage)
-40 … +70 °C
Processing temperature
-25 … +50?°C
Temperature range of connection cable
≥ (Tambient+ 30 K)
Relative humidity
5 … 85?% (no condensation permissible)
Operating altitude (max.)
2000m
Standards/specifications
EN 50121-3-2
WAGO Basic Relay
857-151
eCl@ss 10.0
27-37-16-01
eCl@ss 9.0
27-37-16-01
ETIM 9.0
EC001437
ETIM 8.0
EC001437
ECCN
NO US CLASSIFICATION
PU (SPU)
25?(1)?pcs
Packaging type
box
Country of origin
DE
GTIN
4050821854241
Customs tariff number
8536490050
CAS-No.
1303-86-2
REACH Candidate List Substance
2,2',6,6'-tetrabromo-4,4'-isopropylidenediphenol
RoHS Compliance Status
Compliant,With Exemption
RoHS Exemption
6(c)
SCIP notification number (Austria)
0891d92a-b9b0-4855-a374-3f4c7d8bcec6
SCIP notification number (Belgium)
3d6ce96b-95c2-45ca-9c75-c48432a5185f
SCIP notification number (Bulgaria)
3eb596a0-fb70-479d-aa2f-992ee8d6da2a
SCIP notification number (Czech Republic)
b067e2e6-b27e-489d-b6ce-e8a58bf12ab3
SCIP notification number (Denmark)
736ec7f4-e597-4f9a-9f8d-e6e1d89224cb
SCIP notification number (Finland)
0e46608a-ada5-42bc-a1e2-3cd98f6f5117
SCIP notification number (France)
ce145d34-e7ee-4421-ba57-5016df2c4aa9
SCIP notification number (Germany)
cf5584f3-5fcd-4275-b373-70c672f11f18
SCIP notification number (Hungary)
7b26aae5-cb7d-40b7-becb-f97e3d03ff32
SCIP notification number (Italy)
d63eee63-1ca0-49a7-bcf1-e4345d48419d
SCIP notification number (Netherlands)
ce9882fe-9872-4be0-9614-5bcdf964b46a
SCIP notification number (Poland)
1482eef4-4a89-4cd2-bd10-fe7e0efba63f
SCIP notification number (Romania)
a3805355-5493-4993-bb06-a6fab5877d65
SCIP notification number (Sweden)
75a7959b-0f84-4330-8630-470a2d3b43e1
Nominal input voltage U<sub>N</sub>
AC/DC?24 … 230?V
Input voltage range
-30 … +10?%
Nominal input current at U<sub>N</sub>
4?mA (230?VAC);?20?mA (24?VDC)
Nominal frequency range (input voltage)
50 … 60?HzAC?/ 0?HzDC
Number of changeover contacts
1
Contact material (relay)
AgNi + Au
Limiting continuous current
6?A
Inrush current (resistive) max.
(AC) 20?A?/ 0.02?s
Switching Voltage, Max.
AC?250?V
Switching power (resistive) max.
AC?1500?VA;?DC (see load limit curve)
Switching capacity
AC-15:?3?A?/ AC?250?V;?DC-13:?2?A?/ DC?24?V
Recommended minimum load
1?V?/ 1?mA?/ 1?mW
Pull-in time (typ.)
15ms
Drop-out time (typ.)
25ms
Bounce time (typ.)
3.5ms
Electrical life (NO; resistive load; 23?°C)
50?x 103 switching operations
Mechanical life
5?x 10? switching operations
Switching frequency with/without load (max.)
6?min-1/ 60?min-1
Status indicator
Yellow LED

Specifications may be subject to change without notice