wago 870-831

Selling Points

  • 1High Voltage Rating: 500V for reliable electrical connections.
  • 2Durable Construction: Made from polyamide (PA66) for long-lasting performance.
  • 3Easy Wiring: Front-entry wiring with CAGE CLAMP connections for quick and secure wire management.
  • 4Compact Design: Slim profile with a pitch of 5.0 mm, ideal for space-saving applications.
  • 5Certified and Approved: Meets international standards including EN 60947 and UL 1059 for added safety and reliability.
Product Details
870-831
wago

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Safety information
Max. insulation diameter: 4.4 mm
Clamping units
4
Total number of potentials
1
Number of levels
1
Width
5?mm?/ 0.197?inches
Height
55?mm?/ 2.165?inches
Depth from upper-edge of DIN-rail
27.5?mm?/ 1.083?inches
Design
horizontal type
Mounting type
DIN-35 rail
Marking level
Side marking
Note (material data)
Information on material specifications can be found here
Color
gray
Material group
I
Insulation material (main housing)
Polyamide (PA66)
Flammability class per UL94
V0
Fire load
0.118MJ
Weight
7.3g
Processing temperature
-35 … +85?°C
Continuous operating temperature
-60 … +105?°C
Product Group
16 (Rail Mounted Terminal Blocks with CCC)
eCl@ss 10.0
27-14-11-20
eCl@ss 9.0
27-14-11-20
ETIM 9.0
EC000897
ETIM 8.0
EC000897
ECCN
NO US CLASSIFICATION
PU (SPU)
100?pcs
Packaging type
box
Country of origin
DE
GTIN
4045454094621
Customs tariff number
8536904000
RoHS Compliance Status
Compliant,No Exemption
Ratings per
IEC/EN 60947-7-1
Rated voltage (III / 3)
500V
Rated impulse voltage (III / 3)
6kV
Rated current
24A
Legend (ratings)
(III / 3) ? Overvoltage category III / Pollution degree 3
Power loss, per pole (potential)
0.766W
Rated current I<sub>N</sub> for specified power loss
24A
Resistance value for specified, current-dependent power loss
0.001Ω
Connection technology
CAGE CLAMP?
Actuation type
Operating tool
Connectable conductor materials
Copper
Solid conductor
0.08 … 2.5?mm2?/ 28 … 12?AWG
Fine-stranded conductor
0.08 … 4?mm2?/ 28 … 12?AWG
Fine-stranded conductor; with insulated ferrule
0.08 … 1.5?mm2?/ 28 … 14?AWG
Strip length
6 … 7?mm?/ 0.24 … 0.28?inches
Wiring direction
Front-entry wiring
Test specification <br/>Railway applications – <br/>Rolling stock – <br/>Electronic equipment
DIN EN 50155 (VDE 0115-200):2022-06
Test procedure <br/>Railway applications – <br/>Rolling stock equipment – <br/>Shock and vibration tests
DIN EN 61373 (VDE 0115-0106):2011-04
Spectrum/Installation location
Service life test, Category?1, Class?A/B
Function test with noise-like vibration
Test passed according to Section 8 of the standard
Frequency
f1= 5 Hz to f2= 150 Hz
Acceleration
5g (highest test level used for all axes)
Test duration per axis
5 h
Test directions
X, Y and Z axes
Monitoring for contact faults/interruptions
Passed
Voltage drop measurement before and after each axis
Passed
Simulated service life test through increased levels of noise-like vibration
Test passed according to Section 9 of the standard
Extended test scope: Monitoring for contact faults/interruptions
Passed
Extended test scope: Voltage drop measurement before and after each axis
Passed
Shock test
Test passed according to Section 10 of the standard
Shock form
Half sine
Shock duration
30 ms
Number of shocks per axis
3 pos. und 3 neg.
Vibration and shock stress for rolling stock equipment
Passed