Product Model
3VA2340-6HM42-0AA0

Selling Points
- 1Designed for 4-pole applications with a breaking capacity of 85 kA at 415 V.
- 2Operates at AC-1 conditions with 6,000 switching cycles at 380/415 V and 5,000 cycles at 690 V.
- 3Offers In=400A overload protection and Ir=160A...400A short-circuit protection.
- 4Provides adjustable ground-fault protection with Ig=0.2...1 x In and tg=0.1/0.3s.
- 5Meets compact dimensions with a height of 248 mm and width of 184 mm, ideal for various mounting options.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Rated Service Breaking Capacity Ics(kA):@400V or 415V | 85 | Rated Voltage(V): | 690 |
Number of Poles: | 4P | Description | 3VA2H400 R400 ETU330 F/4P; 3VA2_400 dimensions; Rated current 400A; Interrupting rating H:85kA; Trip unit ETU330; |
Mounting Method: | F: Fixed | Trip Unit: (If required is not in the list, reset and select the trip unit first) | ETU330 [Electronic LIG] |
Rated Ultimate Breaking Capacity Icu(kA):@400V or 415V | 85 | Interrupting Rating: | H:85kA |
Rated Current In(A): | 400 | Specifications: | 400 [250-400A] |
Lifecycle | Delivery Release (PM300) | Country of Origin | China |
ECCN | 9N9999 | AL | N |
Model Number | 3VA2340-6HM42-0AA0 |
Specifications may be subject to change without notice