Product Model
3VM1112-4GD42-0AA0

Selling Points
- 1Provides comprehensive protection against overloads and short circuits with thermal-magnetic trip units.
- 2Offers a compact frame size with a mounting depth of 70 mm and cover size of 45 mm, ideal for plant area installations.
- 3Features a universal platform of accessories that can be easily installed across all sizes, saving time and reducing costs.
- 4Available in 1-pole to 4-pole versions with rated operational currents ranging from 16 A to 630 A and rated voltages up to 500 V.
- 5Meets IEC / EN 60947-1, IEC / EN 60947-2, and IEC / EN 60947-3 standards for electromagnetic compatibility and safety.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Rated Service Breaking Capacity Ics(kA):@400V or 415V | 27 | Rated Voltage(V): | 415 |
Number of Poles: | 4P | Description | 3VM1S160 R125 TM210N F/4P; Size 160; Rated Current 125A; Interrupting Rating S:36kA; Trip Unit TM210N; |
Mounting Method: | F: Fixed Mounting | Trip Unit: (If required is not in the list, click reset, select trip unit first) | TM210N [LI fixed, with N-phase protection] |
Rated Ultimate Breaking Capacity Icu(kA):@400V or 415V | 36 | Interrupting Rating: | S:36kA |
Rated Current In(A): | 125 | Specifications: | 160 [8-160A] |
Lifecycle | Delivery Release (PM300) | Country of Origin | China |
ECCN | N | AL | N |
Model Number | 3VM1112-4GD42-0AA0 |
Specifications may be subject to change without notice